Open-Flued Ventilation
Room-vent calculation with an explicit input allowance.
Method: Approved Document J, England — stated room-vent conditions
Practise a room-vent calculation with the allowance stated explicitly. Establish the appliance and building conditions before choosing a method.
Room-vent calculation with an explicit input allowance.
Method: Approved Document J, England — stated room-vent conditions
This exercise uses the room-vent method in Approved Document J for England for specified flued gas appliances. It excludes decorative fuel effect fires, flueless appliances and compartment openings. The 7 kW allowance is conditional: the guidance links it to older dwellings with air permeability above 5 m³/(h·m²). It is not a universal exemption for small appliances.
Calculated area (cm²) = max(0, total rated net input kW − permitted allowance kW) × 5. The calculator starts with no allowance. Select 7 kW only when the exercise or applicable design conditions establish that it is permitted.
Check the appliance instructions, air route and applicable requirements separately. Room-sealed combustion air and compartment cooling are different checks. This room calculation does not specify all ventilation needed for every installation.
At 20 kW net, no allowance gives 20 × 5 = 100 cm². Where the 7 kW allowance is permitted, (20 − 7) × 5 = 65 cm².
There are 100 mm² in 1 cm², because both dimensions are multiplied by ten: 10 mm × 10 mm = 100 mm². Multiply cm² by 100 to get mm², or divide mm² by 100 to get cm². The 65 cm² result above is therefore 6500 mm², not 650 mm².
This also helps when reading vent specifications. A stated free area of 6000 mm² is 60 cm², so it is smaller than a calculated requirement of 65 cm². Compare the free-area figures in the same units before choosing a vent.
The outside dimensions include solid material. A grille measuring 150 mm × 100 mm covers 15,000 mm², or 150 cm², but that is not necessarily its open area. In a hypothetical exercise where 40% is open, free area would be 150 × 0.40 = 60 cm²: still short of 65 cm².
Use the manufacturer’s declared equivalent area for the complete vent assembly where available. Do not assume a percentage from its appearance, treat the nominal duct diameter as its capacity, or add unsuitable flyscreen to a gas-appliance air vent.
Identify the appliance and where its air supply comes from before applying a rule. This result does not specify the high- and low-level openings for a cupboard or compartment. Dividing a room result in half does not establish the size of those openings; their purpose, position and route to air must follow the applicable procedure.
The flue flow and spillage guide explains the separate checks on the combustion-product route. Use it alongside the ventilation calculation, and the gas-fire revision notes when studying heater-specific scenarios.
Under the stated 5 cm²/kW room-vent method, 20 kW net gives 100 cm² without an allowance, or 65 cm² where the 7 kW allowance is permitted. Appliance type, room arrangement, air permeability and instructions determine whether that method and allowance apply.
A room-sealed appliance takes its combustion air from outside through the flue arrangement, so it does not need a purpose-provided combustion vent in the room. Compartment cooling and manufacturer instructions can still apply.
An openable window cannot replace a required permanent combustion-air vent because it can be closed. It may have a separate rapid-ventilation role for an appliance whose instructions require that provision.
Method: Approved Document J, England — stated room-vent conditions
Something wrong, unclear or out of date? Report an issue with this calculator.
Training & revision aids — live installations follow the full standard, the manufacturer’s instructions and calibrated instruments.